ICT (Induced Draft Counter flow Cooling Tower) Round shaped or popularly
known as bottle type are designed to cool industrial re-cycled process water
from temperature of 50 degrees to temperature of 4 plus the prevailing Wet
Bulb temperature of the region.
The tower design incorporates hot water inlet at the bottom collection sump
circulated vertically to the mechanical rotary sprinkler located above the fill
media. The inlet water pressure rotate the sprinkler, having extended arm
pipes with orifices to disperse water uniformly over the fill media.
The fan directly coupled to the motor, during operations takes away the heat by
induced draft mechanism. Air is drawn from the lower air in take area & is
induced to travel through the fill media thus taking away the latent heat from
the water passing through the fill media. Portion of water evaporated, removes the heat from the remaining water. The warm moist
air is drawn through the fan deck is discharged to the atmosphere. Cold water, collected at the collection sump, is re-circulated to the
source.
Warm water from the heat source is circulated to the water distribution system. The water is dispersed uniformly over the wet deck fill by means of orifice of the extended arm pipes of the rotary sprinkler. Simultaneously, air is drawn in through the air inlet louvers at the base of the tower and travels upward through the wet deck fill opposite to the direction of the water flow. A small portion of the water is evaporated which removes the heat from the remaining water. The warm moist air is drawn to the top of the cooling tower by the fan and discharged to the atmosphere. The cool water drains to the basin at the bottom of the tower and is returned to the heat source.
All structural in HDG Steel to arrest rust
PVC Fills with varying flute sizes of 12 mm, 14 mm, 19 mm, 22 mm to increase the contact surface area.
TEFC, IP-55 Protected 'F' Class Insulated motor with extended shaft to assist outdoor applications.
Adjustable pitch axial flow, dynamically balanced aluminium fans to improve the air exhaust at minimum power usage.
Casings of FRP (Fibre Reinforced Plastics) for durability and strength
All joints fastened with SS fasteners to arrest rust
Uniformity in water dispersion through rotary sprinkler
Capacities 10TR to 600TR , in single cell
Water flow 5 CMH to 500 CMH, in a single cell
360 Degrees air intake area assist 100% cooling efficiency
Delta T (Temperature drop) 4Deg C to 30Deg C, in single cell
ABS Fills for high temperature applications (150Deg C)
All structural in HDG Steel to arrest rust
PVC Fills with varying flute sizes of 12 mm, 14 mm, 19 mm, 22 mm to increase the contact surface area.
TEFC, IP-55 Protected 'F' Class Insulated motor with extended shaft to assist outdoor applications.
Adjustable pitch axial flow, dynamically balanced aluminium fans to improve the air exhaust at minimum power usage.
Casings of FRP (Fibre Reinforced Plastics) for durability and strength
All joints fastened with SS fasteners to arrest rust
Uniformity in water dispersion through rotary sprinkler
Capacities 10TR to 600TR , in single cell
Water flow 5 CMH to 500 CMH, in a single cell
360 Degrees air intake area assist 100% cooling efficiency
Delta T (Temperature drop) 4Deg C to 30Deg C, in single cell
ABS Fills for high temperature applications (150Deg C)
Aluminium die casting m/c
Air compressors
A/C plant & cold rooms
Blow moulding M/c
Chemical industries
Dairy,Citrus and other food processing industries
Distilleries and Breweries plants
Diesel / Gas Gensets & Megawatt Projects
Glass Mfg. Plant
Herbal,Aromatics & extraction plants
Industries heat process
Oil refineries
Plastic injustion moulding m/c
PVC pipes mfg.plant
Soap / Cosmetic mfg. industries
Steel factory and foundry